OP is correct, the people making fun of OP don't have an engineering background.

The pressure of a condenser at 90F (hot summer day) is about 1/20th of an atmosphere and ... pretty obviously the pressure of a condenser at 212F is about one atmosphere. You can't just arbitrarily decide to change the low pressure side of a turbine like that, its not going to turn out well. You could, in theory, design an entire thermal plant coolant loop to deal with the condenser running at 1 atm instead of 1/20th atm but most will not.

There are also heat flow rate issues where the higher the delta V the higher the watts. Regardless of condenser pressure issue above, if a heat exchanger can pull 1 MW across a 150 degree delta-V then if you run the cold side much warmer at only 15 degrees delta V it can only "pull" 0.1 MW of heat. Its surface area doesn't magically get bigger LOL. Remember that for every watt of electricity you get to dump around three watts of thermal heat. If you lose 9 MW of cooling power you lose 3 MW of output electrical power. You have to move more heat than non-engineers expect, to generate electricity.

Its a simplification, but for various reasons they like to design the hot side as hot as possible, so if you lose 100F of cooling you can't keep the same power output and simply run the hot side 100F hotter than normal and keep the same flow rate. Absolutely nothing good will come from overheating it like that.

You could engineer a thermal plant (thermal as in coal, nuclear, burning recyclables and biowaste, anything to make steam) that runs at an ideal hot side of 212F and let the hot side literally boil water in a pool. However, they don't make plants like that IRL and trying to force it under those conditions would turn out very bad... The first thing that comes to mind is gunk buildup and higher corrosion rates. Steel (generically speaking) corrodes in water about twice as fast per every 20C increase, so turning a cold water plant into a water boiler would to first approximation cause about a year's worth extra corrosion per month. Could be designed around, but I would not want to cowboy a nuke and just try it. Some of those parts are very expensive; even if you can safely run the plant and replace the corroded parts at a substantially accelerated rate, the cost of power due to corroding the cold side parts might make the power too expensive even if its "safe enough", making it cheaper to just shut down. Moving large amounts of water (or air) is extremely expensive, both capex and opex, so an additional 10x higher once in awhile here and there could be a lot of money...