I agree with you, but. The NEC has an 80% rule for continuous loads (over 3 hours) that use a typical circuit breaker as overcurrent protection. If you use fuses or a 100% rated breaker as your over current protection, then you can use all of the available ampacity. Anyways, devices that use a 15A receptacle (for example) will not draw more than 12A continuous if they’re meant to run continuously (3 hours or longer).

https://www.se.com/us/en/faqs/FA104355/